ROI designed a retrofit for this
building that converted it from an undersized HVAC system, incapable of providing comfort
in a building with only 30% occupancy, to a system that routinely handles 450 people per
floor, an occupant density of 15 per thousand, or approximately 1.6 times greater than a
standard office facility is designed for.
The
occupancy level has increased six-fold since we undertook this project, and we are still
serving the tenants with the same fan and duct riser system that was incapable of meeting
the needs of the nearly see-through facility, prior to our project.
We converted
the system from a normal air temperature system to a low temperature air
system, capable of meeting peak loads by providing supply air as cold as 39°F as needed.
Through
careful equipment selections, and substantial HVAC system automation, the chiller plant
operates at less than 0.60 kW per ton,
including the chillers, pumps and cooling tower fan energy. On mild days when most HVAC systems are at their
worst efficiencies, our entire chiller plant system operates in the 0.45 kW per ton range.
The
conversion to Low Temperature Air reduced peak fan horsepower by 45%, and reduced the
first cost of the retrofit by approximately $500,000 when compared to the alternate
solutions provided by competing firms. |